DANGER OF ELECTRIC SHOCK
-
This Equipment must be installed and serviced only by qualified electrical personnel
-
Isolate area of works so there is no power running through the unit during the installation process
-
Wear safety goggles during the install and take precautions before starting work
-
Check the unit and IRISS window has been installed
-
correctly and that there is no debris, etc in the unit before switching back on the power
REMEMBER
Under no circumstances should any IR window be fitted within the following minimum dialectric clearances!
5 Kv Equipment no less than 4 inches!!
15 Kv Equipment no less than 6 inches!!
Under no circumstances can the minimum clearances be compromised |