   home > infrared > vp-75
IRISS

Infra Red Inspection Support Systems


Fitting Instructions


VP-75 Series

 

VP50 Contents

Parts List

  • 1 IRISS VP75 Assembly
  • 1 Thrust Ring
  • 5 Fixing Screws
  • 1 Fitting Label
  • 1 Instruction Label
  • 1 Window ID Label

 

Tools

Recommended Tools

  • 1 Electric Drill
  • 1 Centre Punch
  • 1 Hammer
  • 5mm Drill Bit
  • 22mm Hole Saw / Cone Drill
  • 1 Electro Hydraulic Punch set
  • 1 50mm Hole Punch
  • 1 Phillips Screwdriver

Warning

DANGER OF ELECTRIC SHOCK

  • This Equipment must be installed and serviced only by qualified electrical personnel
  • Isolate area of works so there is no power running through the unit during the installation process
  • Wear safety goggles during the install and take precautions before starting work
  • Check the unit and IRISS window has been installed correctly and that there is no debris, etc in the unit before switching back on the power

REMEMBER

Under no circumstances should any IR window be fitted within the following minimum dialectric clearances!

5 Kv Equipment no less than 4 inches!!

15 Kv Equipment no less than 6 inches!!

Under no circumstances can the minimum clearances be compromised

 

Peel off the backing of the template and place the fitting template supplied with your IRISS window in the position that you wish to fit the window.

NOTE:
The Fitting Template must be fitted to the front of the panel that you intend to fit the IR window.

Please keep the backing as this contains the instructions for the installation of your window

VP75 Step 1

  1  

 

Using a centre punch mark all the drilling points and then using a 22mm holesaw or cone drill cut a hole where indicated in the centre of the label.

 

VP50 Step 2

  2  

 

Using a 5mm drill bit drill out the 3 fixing holes where indicated on the label.

 

VP75 Step 3

  3  

Using the electro-hydraulic punch and the 50mm cutting die, cut out the 50mm hole where indicated. We would recommend that you read and follow the manufacturers instructions prior to completing this phase of the installation
NOTE:
Use a file to clean any burrs from the fitting face if required.

VP75 Step 4

  4  

Line up the IRISS window with the gaskets on the outside of the panel / assembly, align the 3 fixing holes and insert the 3 screws through the thrust plate into the main body.

Tighten the screws to 0.2Nm (Fully by hand) and replace the panel into its normal operating mode.

VP75 Step 5

  5  

Ensure that the front cover is fixed into position.Your IRISS window is now ready for use.

CAUTION
This device is incomplete without the cover fitted

VP75 Step 6

  6  


Related Documents